• Intelligent Pre-Fabricated Substation-1000kVA for Industrial Park
  • Intelligent Pre-Fabricated Substation-1000kVA for Industrial Park
  • Intelligent Pre-Fabricated Substation-1000kVA for Industrial Park
  • Intelligent Pre-Fabricated Substation-1000kVA for Industrial Park
  • Intelligent Pre-Fabricated Substation-1000kVA for Industrial Park
  • Intelligent Pre-Fabricated Substation-1000kVA for Industrial Park

Intelligent Pre-Fabricated Substation-1000kVA for Industrial Park

Type: Distribution Metering Box
Structure: Protection
Certification: ISO9001:2000, CCC
Form: All- packaged Type
Operation Voltage: High Voltage
Size: 3 Uint

Contacter le Fournisseur

Membre Diamant Depuis 2022

Fournisseurs avec des licences commerciales vérifiées

Fabricant/Usine

Info de Base.

N° de Modèle.
YBM22-1000/10
Application Range
High-rise Buildings
Shell Material
Stainless Steel
Shell Protection Grade
IP55
Brand
Sce
Paquet de Transport
Wooden Case
Marque Déposée
SCE
Origine
China
Code SH
8537201000
Capacité de Production
980 Sets/Year

Description de Produit

This series substation follows Standard: GB17467-1998; And relative IEC standard.
This substation is a combination of High Voltage Cabinet, Low Voltage Cabinet and Transformer.
 
Main Technical Parameters for HV Switchgear
No. Item Unit XGN-12(F) XGN-12(F. R) XGN15-12(F) XGN15-12(F. R)
1 Rated Voltage KV 12
2 Rated Insulation Level Rated Short-time Power-frequency Withstand Voltage KV Phase-to-ground Voltage & phase-to-phase Voltage: 42,
Disconnector Break Voltage: 48
Rated Lightning Impulse Withstand Voltage Phase-to-ground Voltage & phase-to-phase Voltage: 75,
Disconnector Break Voltage: 85
3 Rated Frequency Hz 50
4 Rated Current Main Busbar A 630
Load Switch 630 Depend on Fuse 630 Depend on Fuse
5 Rated Current of Fuse A   125   125
6 Rated Short-time Withstand Current   20
7 Rated Peak Withstand Current   50
8 Duration Time of Rated Short-time Withstand Current(Main Loop) S 3 3 3 3
9 Duration Time of Rated Short
time Withstand Current(Grounded Loop)
S 2 2 2 2
10 Rated Short-circuit Making Current KV 50
11 Rated Short-circuit Breaking Current KV   31.5(Prediction)   31.5(Prediction)
12 Rated Breaking Current Active-power Load Current A 630   630  
Close-loop Breaking Current A 630   630  
Cable Charging Current A 10 10 10 10
13 Rated Take-over Current A   3150    
14 Rated Transfer Current A       1700
15 Protection Degree     IP3X
16 Mechanical Endurance Times 1000 2000




Intelligent Pre-Fabricated Substation-1000kVA for Industrial ParkIntelligent Pre-Fabricated Substation-1000kVA for Industrial ParkIntelligent Pre-Fabricated Substation-1000kVA for Industrial ParkIntelligent Pre-Fabricated Substation-1000kVA for Industrial Park

 

Envoyez votre demande directement à ce fournisseur

*De:
*A:
*Message:

Entrez entre 20 à 4000 caractères.

Ce n'est pas ce que vous recherchez? Publier la Demande d'Achat Maintenant